Remo

Closing a control loop across a network that can fail.

The controller, the sensor and the actuator of a PID loop run as three separate services. The loop keeps control while the network between them is healthy, and fails safe when it isn't.

CI Java 21 Dependencies Since License: MIT

Remo dashboard: the loop settles on its setpoint, the sensor link is cut and the controller holds, goes fail-safe and recovers; then the actuator link is cut and its watchdog closes the valve.

Remo stands for remote. It began as my master's dissertation, Remote Control (Technical University of Cluj-Napoca, 2014), and was rebuilt from scratch in 2026.

What Remo solves

Remo answers one question: how do you run a feedback loop when the sensor and the actuator are somewhere else, and the network between them can't be trusted?

  1. It distributes the loop.
    • Every element of the loop is an independent service with a small HTTP contract: the controller, the actuator (the thesis's execution element) and the sensor (the transducer).
    • The controller can run next to the process or far from it, the split the thesis proposed: "controller located locally or remotely; actuator remote; transducer remote".
  2. It controls any process, tuned while running. Any process described by a gain, a lag and a dead time can be controlled. The setpoint, the PID gains, the direction, the mode and the process itself all change live. This is the thesis's aim of a "generic implementation of process control, made concrete by setting (even in real time) the transfer function and the PID".
  3. It survives the network.
    • Every call has a deadline, and stale or missing readings never reach the PID.
    • A lost sensor leads to holding the last output, then to a safe output, then to a smooth return.
    • A lost actuator freezes the integral term, so it can't build up while the output isn't taking effect.
  4. It fails safe at both ends. The controller moves to a safe output when it goes blind. The actuator has its own watchdog, so the valve closes even if the controller disappears entirely.
  5. It makes all of this visible and testable.
    • Every network link can be cut, slowed down or made lossy at runtime.
    • A live dashboard shows each request as it happens.
    • Automated tests prove each fault path, including over real sockets.

Where this applies

  • Telecontrol. Pumping stations, substations and pumped-storage plants have long been operated from a central control room over telemetry links. This was the thesis's starting point.
  • Distributed control systems and Industrial IoT. Here the controller increasingly runs on an edge box or in the cloud, away from the equipment.
  • Teaching networked control. The dashboard shows what a lost packet, a late answer or a dead link does to a real loop, and what a good fault policy does about it.

Scope. The process is simulated, and Remo is a reference design, not a certified safety system. The services have no authentication or TLS, by design, to keep the example small, so run them only on a trusted network.

The problem

A textbook control loop assumes the controller, the sensor and the actuator are wired together. Once a network sits between them, the loop inherits the network's faults: latency, dropped messages, and links that simply go away. The 2014 thesis saw this first-hand when it cut its remote command service: "if the command doesn't rise, the measured value doesn't rise."

A naive loop fails in dangerous ways when that happens:

Failure Naive loop Consequence
The sensor doesn't answer Treats the missing reading as 0 The error equals the full setpoint, so the controller opens the valve fully
The actuator doesn't answer Keeps integrating the error The integral winds up; when the link returns, the output slams to the limit
A reply arrives late Waits for it The sample period stretches, and the tuning no longer matches reality
The controller dies Nothing on the field side reacts The valve stays wherever it was last put

The 2014 version had the first of these bugs. The rebuild handles all four.

How Remo handles each failure

  • Every remote call has a deadline. Each call must answer within 40% of the sample period (40 ms at the default 100 ms). A slow answer counts as a lost one, so a sample never overruns. Actuator commands carry that expiry and an increasing sequence, so a timed-out or out-of-order command cannot take effect later. If only its acknowledgement is lost, the controller reconciles the sequence before sending another command.
  • A missing reading is never treated as data. The PID only sees fresh readings. The sensor reports the age of its value, and a stale value counts as missing.
  • A sensor loss is handled in stages.
    1. HOLDING: keep the last output that was applied.
    2. FAIL_SAFE: if the sensor stays lost for 3 s, move to the configured safe output.
    3. Recovery: re-initialise the PID from the output in effect, so control resumes without a bump.
  • No windup while the actuator is unreachable. The controller stops integrating and keeps retrying the last output that was actually applied.
  • The field side protects itself. The actuator has a watchdog: if commands stop for 1 s, it closes the valve on its own. It doesn't depend on the controller being reachable to fail safely.
  • Tuning doesn't depend on the sample rate.
    • Gains are per second, and each step uses the time that actually elapsed.
    • The derivative acts on the measurement, so a setpoint change causes no derivative kick.
    • Conditional integration stops the integral from driving a saturated output farther past its limit (anti-windup).
  • The simulated process behaves like a physical one.
    • First order with dead time, discretised exactly.
    • It runs on its own clock in the sensor service.
    • It is driven by the valve position the actuator actually applied, not by what the controller hoped for.
  • Faults are built in. Any network link can be cut, slowed down or made lossy at runtime, from the dashboard or the API.

Architecture

flowchart LR
    B["Browser<br/>dashboard"]
    subgraph room["Control room"]
        C["<b>Controller</b><br/>PID loop<br/>:8080"]
    end
    subgraph field["Field"]
        direction TB
        A["<b>Actuator</b><br/>valve + watchdog<br/>:8082"]
        P[("<b>Process</b><br/>K·e^(−Ls) / (Ts+1)")]
        S["<b>Sensor</b><br/>measures the process<br/>:8081"]
        A == valve position ==> P
        P == process value ==> S
    end
    C -- "POST /command<br/>over the network" --> A
    S -- "GET /reading<br/>over the network" --> C
    C -. "server-sent events" .-> B
Loading

Each service is a plain Java class on the JDK's built-in HTTP server with virtual threads. The only library is Jackson, for JSON. The three services can run in one JVM or on three machines.

One control step

sequenceDiagram
    autonumber
    participant C as Controller
    participant S as Sensor
    participant A as Actuator
    C->>S: GET /reading (timeout 40 ms)
    S-->>C: { value, ageMillis }
    Note over C: stale or missing? HOLDING / FAIL_SAFE<br/>otherwise u = PID(setpoint, value, Δt)
    C->>A: POST /command { value: u, sequence, expiry } (timeout 40 ms)
    A-->>C: { applied, watchdogTripped, lastSequence }
    Note over C: no answer? freeze the integrator,<br/>retry the last applied output
    loop every 50 ms, on the physical side
        S->>A: GET /state (the valve position drives the process)
    end
Loading

Loop states

stateDiagram-v2
    direction LR
    [*] --> RUNNING
    RUNNING --> HOLDING: sensor or actuator lost
    HOLDING --> FAIL_SAFE: sensor lost for more than 3 s
    HOLDING --> RUNNING: link back (bumpless)
    FAIL_SAFE --> RUNNING: sensor back (bumpless)
    RUNNING --> MANUAL: operator takes over
    MANUAL --> RUNNING: operator hands back (bumpless)
Loading

The control theory

PID controller (PidController). This is the positional form. $\sigma = +1$ for direct acting and $-1$ for reverse acting (e.g. cooling). $\Delta t_k$ is the measured time since the previous step:

$$e_k = \sigma (SP - PV_k)$$

$$I_k^* = I_{k-1} + K_i e_k \Delta t_k$$

$$u_k = \mathrm{clamp}\Big(K_p e_k + I_k - \sigma K_d \frac{PV_k - PV_{k-1}}{\Delta t_k}\Big)$$

$I_k = I_{k-1}$ when $I_k^$ would drive an already saturated output farther past its limit; otherwise $I_k = I_k^$. This is conditional-integration anti-windup.

  • A bumpless transfer balances the terms as $I := u - P - D$ and primes the previous measurement, so proportional and derivative action cannot be reapplied on top of the output already in effect.
  • The defaults ($K_p = 2.5$, $K_i = 0.3~\mathrm{s^{-1}}$) follow Skogestad's SIMC rule for the default process.

Process (FirstOrderPlant). This is first order with dead time, with gain $K$, lag $T$ and dead time $L$. It is discretised exactly for a zero-order-hold input with step $\Delta t$:

$$G(s) = \frac{K e^{-Ls}}{Ts + 1} \qquad\Longrightarrow\qquad y_{k+1} = a y_k + K(1-a) u_{k-d},\quad a = e^{-\Delta t/T},\quad d = \mathrm{round}(L/\Delta t)$$

The defaults are $K = 1.5$, $T = 8~\mathrm{s}$ and $L = 1~\mathrm{s}$: a slow process with a noticeable delay, like a heated tank.

Quick start

You need JDK 21 and Maven.

mvn package
java -jar target/remo.jar

Open http://localhost:8080. Then:

  • Cut the sensor link. Click the lower network link in the diagram. Watch the controller hold its output, go fail-safe after 3 s, and resume without a bump when you click again.
  • Cut the actuator link. Click the upper link. The actuator's own watchdog closes the valve and the process drops.
  • Slow the network. Add 60 ms of latency. Answers now miss the 40 ms deadline and count as lost.
  • Change the process. Raise the dead time to 4 s. The same gains now oscillate; retune to Kp 1 and Ki 0.1.
  • Watch it run on its own. Turn on demo mode to get a new setpoint every 20 s.

Running the services separately

Each service can run as its own process, for example on different machines:

REMO_BIND_HOST=0.0.0.0 java -jar target/remo.jar actuator
REMO_BIND_HOST=0.0.0.0 REMO_ACTUATOR_URL=http://field-box:8082/ java -jar target/remo.jar sensor
REMO_BIND_HOST=0.0.0.0 REMO_SENSOR_URL=http://field-box:8081/ REMO_ACTUATOR_URL=http://field-box:8082/ java -jar target/remo.jar controller

Services bind only to loopback by default. Setting REMO_BIND_HOST=0.0.0.0 exposes their unauthenticated HTTP APIs, so use it only on a trusted network. Hosts must keep their clocks synchronized because actuator command deadlines use epoch time.

Variable Default
REMO_BIND_HOST 127.0.0.1
REMO_CONTROLLER_PORT / REMO_SENSOR_PORT / REMO_ACTUATOR_PORT 8080 / 8081 / 8082
REMO_SENSOR_URL / REMO_ACTUATOR_URL http://localhost:<port>/

HTTP API

Service Endpoint Purpose
Controller GET / · GET /events Dashboard and live samples (server-sent events)
GET, POST /api/settings Setpoint, gains, direction, auto/manual, demo mode; partial updates
GET /api/history The last 60 s of samples
GET, POST /api/sensor/faults · /api/actuator/faults · /api/plant Forwarded to the field services
Sensor GET /reading { value, ageMillis }, behind fault injection
GET, POST /plant { gain, timeConstantSeconds, deadTimeSeconds }
Actuator POST /command { value, sequence, expiresAtEpochMillis }; ordered and time-bounded
GET /command Last acknowledgement, behind the controller-link fault injection
GET /state { applied, watchdogTripped, lastSequence }, read by the process
Sensor and actuator GET, POST /faults { down, latencyMillis, dropRate }
curl -s localhost:8080/api/settings -d '{"setpoint": 90, "kp": 2}'
curl -s localhost:8080/api/sensor/faults -d '{"down": true}'

Project layout

src/main/java/org/ilu/remo/
├── Remo.java                       launcher: all services, or one by name
├── control/
│   ├── PidController.java          the PID, pure and unit-tested
│   └── ControlLoop.java            fault policy: hold, fail-safe, bumpless recovery
├── plant/FirstOrderPlant.java      the simulated process
├── sensor/SensorService.java       runs the process and answers readings
├── actuator/ActuatorService.java   valve with a watchdog
├── controller/                     runs the loop, streams samples, serves the dashboard
└── http/                           JSON over the JDK HTTP server, fault injection
src/main/resources/web/             the dashboard: one HTML page, plain JS and CSS

Tests

mvn verify runs 30 tests in a few seconds:

  • PidControllerTest checks the PID itself:
    • gain arithmetic;
    • independence from the sample rate;
    • anti-windup;
    • reverse action;
    • no derivative kick;
    • bumpless transfer.
  • FirstOrderPlantTest checks the process model: 63.2% of the step at one time constant, the steady-state gain, the dead time, and parameter validation.
  • ControlLoopTest covers every fault path against an in-memory process with a clock the test controls:
    • settling on the setpoint;
    • hold instead of reading zero;
    • fail-safe;
    • stale readings;
    • bumpless recovery;
    • no windup while the actuator is lost;
    • manual mode.
  • ActuatorServiceTest proves expired and out-of-order commands cannot move the actuator.
  • ActuatorLinkTest proves the controller reconciles a command that was applied when its acknowledgement was lost.
  • HttpTest proves servers bind only to loopback by default.
  • RemoEndToEndTest starts all three services on real sockets. It closes the loop, cuts the sensor link through the API, checks the fail-safe and the recovery, and checks the event stream.

From the 2014 thesis

Classic control loop in which the actuator (EE) and the transducer (T) are marked Remote 2014 architecture: a JSF web app with PV and CMD SOAP consumers, talking to a remote process value service on port 9998 and a remote command service on port 9999
The idea: take the classic loop and make the actuator (EE) and the transducer (T) remote. The 2014 architecture: SOAP services for the process value and the command.

Remote Control (Control de la distanță), a master's dissertation by Ioan-Laurențiu Lucuț.

  • Institution: Technical University of Cluj-Napoca, Faculty of Automation and Computer Science, Automation Department.
  • Supervisor: Conf. Dr. Ing. Eva Dulf.
  • Defended: 17 September 2014.

The thesis set out to "control remote (distributed) processes with the help of web services, by distributing the elements of the control loop". It aimed to be generic: any process with a transfer function could be controlled by a PID whose parameters change at runtime. It was built with Java 7 SOAP services (JAX-WS), a JSF and PrimeFaces web app, Apache Shiro and PostgreSQL. The loop worked, and the thesis showed it with step responses and simulated connection losses.

The 2014 dashboard: transfer function, PID settings, remote service status and a chart of setpoint, process value and command

The original code is preserved at the thesis-2014 tag. Rebuilding it meant revisiting its decisions with twelve more years of experience:

2014 thesis 2026 rebuild
Transport SOAP/WSDL (JAX-WS), generated clients JSON over HTTP on the JDK's own server
Lost sensor or actuator Value taken as 0; the PID keeps running on it Hold, then fail-safe; integrator frozen; bumpless recovery
Actuator Stub that always acknowledged Valve with a watchdog that fails safe on its own
Process Simulated inside the sensor from state sent by the controller; dead time stored but ignored Runs on its own clock, driven by the real valve position; dead time implemented
Tuning Gains tied to a 1 s sample; scaling applied in some code paths but not others Gains per second, scaled by the measured Δt
Stack JSF, PrimeFaces, CDI, Hibernate, Shiro, PostgreSQL, Tomcat One jar, one direct dependency (Jackson)
Tests Integration tests that needed running services 25 automated tests and CI
Java 7 21 (records, virtual threads)

Acknowledgements

Contributing

Issues and pull requests are welcome, especially new process models, other fault policies, or adapters for real sensors and actuators. mvn verify must pass.

License

MIT © 2014–2026 Ioan Lucuț

About

PID control across an unreliable network: a remote sensor and actuator with fault injection, fail-safe recovery and a live dashboard. Master's thesis (TU Cluj-Napoca, 2014), rebuilt in Java 21.

Topics

Resources

Stars

0 stars

Watchers

1 watching

Forks

Releases

Packages

Contributors

Languages